Modbus I/O Module
Integrated Modbus valve control and water metering in one compact module — a simple interface between Modbus host systems and field-installed metering and control equipment.
Designed, built and supported by Ranch Systems · telemetry since 2005
The Ranch Systems RX20 provides a simple interface between Modbus host systems and field-installed metering and control equipment. A dedicated counter input supports compatible pulse-output meters, while the DC latching output provides efficient control of compatible latching valves.
How it connects
In the field
Dry contact or reed switch, 0–100 Hz, into the counter input
±9–12 V DC, driven by the valve output
Counts pulses (with supercap backup) and switches the valve. 12 VDC.
Your system
PLC, controller, SCADA or building management system reads the meter count and commands the valve over Modbus RTU
Already a Ranch Systems customer? Pair the RX20 with an RS10 transmitter to bring readings and valve control into the myRanch™ app.
Mount it at the meter and valve. The RX20 handles the field wiring; your system handles scheduling, alerts and shutoff logic.
Typical Applications
Read pulse-output meters and open or close latching valves from one Modbus device.
Count meter pulses and let your host system close the valve when water is flowing where it shouldn't.
Meter individual units, tenants or buildings using the pulse-output meters you already have.
Add valve control and flow totals to treatment and filtration equipment.
Meter and control reuse systems with a compact, IP68-rated module.
Specifications
| Input voltage | 12VDC |
| Consumption | <1mA, typical (brief surge currents of ~300mA during supercapacitor charging) |
| Protocol | Modbus RTU |
| ID | Programmable via holding register |
| Number of ports | 1 |
| Type | DC latching |
| Compatible valves | +/- 9-12V typical DC solenoid |
| Connection | Terminal block |
| Number of ports | 1 |
| Type | 0-100 Hz pulse counter w/ supercap backup |
| Compatible meters | Dry contact & reed switch |
| Connection | Terminal block |
| Enclosure | PA66 plastic w/ silicone gasket & sealing rings |
| Dimensions | 4.83 × 3.24 × 1.67 in. (122.8 × 82.3 × 42.5 mm) |
| Enclosure IP rating | IP68 |
| Operating temperature | -40°F to 185°F (-40°C to 85°C) |
| Assembled weight | 0.6 lbs (0.27 kg) |
Conversations you start here will show up in this list.